Components / EMC Products / 3-Phase Block Filters / FMAC SINE DCL
FMAC SINE DCL General Information shop
Shop
pdf
pdf-datasheet

Order Number: toset


EMV 3-Phase Block Filter: Sine wave output filter with a voltage dc link

Environment_Safety RoHS   Environment_Safety China-RoHS

Description

Description

Design corresponding to UL 1283, CSA 22.2 No. 8, IEC/EN60939
Enhancement of the system efficiency

Applications

Optimized for long motor cables (up to 1000 m) and operation under full load
Equipped with voltage connection to converter dc link circuit for best results
Frequency converters in uninterruptible power supplies, elevators, heating-, ventilating- and air conditioning-systems, traction and conveyer systems
Cost saving technologie, increase of motor life time, deployment of flexible lightweight unshielded instead of expensive shielded motor cables, reduced fitting work

Weblinks

pdf-datasheet, General Product Information , Approvals, CE declaration of conformity, RoHS , CHINA-RoHS , e-Shop, SCHURTER-Stock-Check, Distributor-Stock-Check, CAD-Drawings , Detailed request for product
Top

Technical Data

Rated Current 4 - 16 A @ Ta 40 °C
Rated voltage 500/288 VAC; 50/60 Hz
Approval for 4 - 16 A @ Ta °C / 500/288 VAC; 50 Hz
Overload Current 1.5 x Ir for 1 minute, per hour
Dielectric Strength 500/288 VAC:
2.5 kVDC between L-L
1.1 kVDC between L-PE
Test voltage (2 sec)
Weight 16 - 24 kg
Material: Housing Metal 
Sealing Compound UL 94V-2 
Mounting Screw-on mounting on chassis, from top
Terminal Screw clamps 
Operating Temperature [°C] -25 °C to 100 °C
Climatic Category 25/100/21 acc. to IEC 60068-1
Degree of Protection IP 20 acc. to IEC 60529
Protection Class Suitable for appliances with protection class I acc. to IEC 61140
Top

Dimension

Dimension

Case 2G
Beschriftung_FMAC_SINE_DCL_Gehäuse 2G
1) Inverter   2) Motor   3) Shield 
4) Shielded cable   5) Endsleeves 
6) Ground   7) Shieldes cable   8) Operation Mode
Case IB
Beschriftung_FMAC_SINE_DCL_Gehäuse IB
1) Inverter   2) Motor   3) Shield 
4) Shielded cable   5) Endsleeves 
6) Ground   7) Shieldes cable   8) Operation Mode
Case 2H
Beschriftung_FMAC_SINE_DCL_Gehäuse 2H
1) Inverter   2) Motor   3) Shield 
4) Shielded cable   5) Endsleeves 
6) Ground   7) Shieldes cable   8) Operation Mode
Case 2I
Beschriftung_FMAC_SINE_DCL_Gehäuse 2I
1) Inverter   2) Motor   3) Shield 
4) Shielded cable   5) Endsleeves 
6) Ground   7) Shieldes cable   8) Operation Mode
Top

CAD


Electrical Data

Diagrams

FMAC Sine_DCL_Block-diagramm_Application_Schaltbild
1) Inverter   2) Ground choke   3) DC-Link  4) Sine wave output filter  5) Motor
Note:
The inverter switching frequency must lie within the range from 2 to 20kHz. A switching frequency below or above the mentioned range will result in poor performances.
Sine wave output filters with dc-link produce leakage currents. These leakage currents could, in combination with certain OEM inverter types, disturb overall system performance, causing a “over current or short to earth�? error message on the inverter. For such cases Schurter suggests the following three solutions or a combination of each:
1) Increasing the switching frequency of the inverter (drawback: increased power loss in the inverter)  
2) Activating the low leakage sine wave output filter operation mode by removing the factory set detachable screw (drawback: light increase of the leakage current in the motor) 
3) Connecting a ground wire choke type DEH in the inverters earth connection (drawback: additional component)
 
FMAC Sine_DCL_Voltage_at_the_motor_Application_Schaltbild
Top


Variants

Tabel of Variants

Rated Current Rated voltage Switching frequency Motor frequency Rated motor power Motor cable lenght DC resistance Total power loss Weight Housing Order Number A=Most Popular [?] MOQ [?] PU [?] e-Shop [?] SCHURTER Stock Check [?] Distributor Stock Check [?]
[A]   [VAC]   [kHz]   [Hz]   [kW]   [m]   [mΩ]   [W]   [kg]                  
         
8 500/288 2...20 0...200 3.0 <= 1000 220 14 16 kg IB FMAC-0SIB-0862 1 1 » » »
4 500/288 2...20 0...200 1.5 <= 1000 450 8 13 kg 2G FMAC-0S2G-0462 1 1 » » »
12 500/288 2...20 0...200 5.5 <= 1000 140 20 20 kg 2H FMAC-0S2H-1262 1 1 » » »
16 500/288 2...20 0...200 7.5 <= 1000 110 28 24 kg 2I FMAC-0S2I-1662 1 1 » » »